Figure 5-52 Teamwork control information screen
----End
5.16 Which Parameters Are Restored to Default Values
After Default Settings Are Operated
After choosing Settings > Restore Defaults > Yes, the following parameters are
displayed:
To prevent loss of important data, record all parameter values before restoring
default settings. After restoring default settings, change the parameter values to
the recorded values.
Issue 12 (2020-10-28)
NO TE
● Master/Slave and Active/Standby indicate the information of this single unit. Other
information is about the teamwork control information of the group.
● Required cooling capacity: indicates the total cooling/heating requirements of the group
and is used as a reference for enabling the cooling/heating mode by the master device.
If the cascade function is enabled, the capacity is used as a reference for determining
whether to start a standby unit.
● Required humidity: indicates the total dehumidification and humidification requirements
of the group and is used as a reference for enabling the dehumidification and
humidification mode by the master device.
All parameters displayed on Settings > System Settings.
All parameters displayed on Settings > Alarm Settings.
All parameters displayed on Settings > Comm Settings.
Date format and time zone settings displayed on Settings > User Settings.
All parameters displayed on Maint > Sensor Adjust.
NO TICE
NO TE
After default settings are restored, all communication addresses are changed to 1 and the
communication between all devices and the EMS is disconnected. The communication
addresses must be reset to recover the communication.