Huawei NetCol8000-A Series User Manual page 172

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A Series:
Table of Contents

Advertisement

NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
Alar
m ID
a012
Issue 12 (2020-10-28)
Alarm
Alar
Occurren
Name
m
ce
Sever
Condition
ity
s
Comp
Major
The
dischar
compresso
ge HT
r
discharge
temperatu
re switch
is
disconnect
ed when
the alarm
detection
delay
expires.
Copyright © Huawei Technologies Co., Ltd.
7 System Operation and Maintenance
Possible Causes
1. The refrigerant
leaks.
2. Cables to the
discharge
temperature switch
are loose or
damaged.
3. The ambient temp
is high.
4. The discharge
temperature switch
is faulty.
5. Outdoor fans are
faulty.
6. The condenser fins
are blocked.
Solutions
1. Check for any
leakages. Fill
refrigerant
after
maintenance
or
replacement.
2. Clean the
condenser
fins.
3. Check the
ambient
temperature.
4. Check cables
to the
discharge
temperature
switch.
5. Maintain or
replace the
discharge
temperature
switch.
6. Maintain or
replace the
outdoor units.
163