7.1.5 Infrared Humidifier

Before removing the water pan from the infrared humidifier, ensure that the
power supply is disconnected and water in the pan is close to the room
temperature and does not cause scalds.
To ensure that the infrared humidifier works efficiently, periodically inspect the
water pan and clean it when necessary. It is recommended that you inspect the
water pan monthly and clean it based on water quality.
Perform periodic maintenance on the infrared humidifier as follows:
Table 7-4 Infrared humidifier maintenance item
No.
1
2
Issue 12 (2020-10-28)
CA UTION
Operations
On the main screen, choose Maint >
Diagnostic Mode > Enter. Start the
humidifier. Check the three phase
currents of the humidifier contact (QC3
for a NetCol8000-A050 unit and QC9
for a NetCol8000-A100 unit) in turn
using a clamp meter. Verify that the
phase currents exist and differ by less
than 20%. The normal current range
for a NetCol8000-A050 infrared
humidifier is 7.5–9 A, and that for a
NetCol8000-A100 infrared dehumidifier
is 12–13.5 A.
Check that water can be smoothly
injected.
Copyright © Huawei Technologies Co., Ltd.
7 System Operation and Maintenance
Troubleshootin
g
Replace it by
referring to
7.4.4 Replacing
the Infrared
Humidifier
Lamps.
If water can
only be injected
to less than 1/3
of the
humidifier, refer
to
7.4.4
Replacing the
Infrared
Humidifier
Lamps
to
remove the
water inlet
valve to check
whether there
are blockages.
Remarks
Perform the
operations
with the
power on.
Perform the
operations
with the
power on.