NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
Alar
m ID
a011
Issue 12 (2020-10-28)
Alarm
Alar
Occurren
Name
m
ce
Sever
Condition
ity
s
Comp
Critic
A
LP lock
al
compresso
r has
triggered
six low
pressure
protection
s within
one
consecutiv
e hour, or
a
compresso
r low
pressure
alarm has
not
cleared
within 30
minutes.
Copyright © Huawei Technologies Co., Ltd.
7 System Operation and Maintenance
Possible Causes
The a010 comp LP
alarm is generated
frequently.
Solutions
Reference to the
solutions for the
a010 comp LP
alarm.
162