● All smart cooling products in a teamwork group must be of the same model.
● Do not directly connect the first and the last smart cooling products to form a
ring network.
Figure 3-50 Teamwork networking
Teamwork Networking and EMS Monitoring
If both teamwork networking and ESM monitoring are required, the smart cooling
product requires a Y-split cable for collecting and transferring information.
3-51
3-53
Figure 3-51 Y-split cable
Figure 3-52 Pin definition of a Y-split cable
Issue 12 (2020-10-28)
NO TICE
NO TE
● The number (n) of smart cooling products in this figure should be less than or equal to
32.
● The teamwork cable between two adjacent smart cooling products must not exceed 10
m in a network.
shows a Y-split cable.
shows the Y-split cable connection for teamwork control.
Copyright © Huawei Technologies Co., Ltd.
Figure 3-52
defines the pins of a Y-split cable.
3 Installation Guide
Figure
Figure
70