NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
Alar
m ID
a031
a032
Issue 12 (2020-10-28)
Alarm
Alar
Occurren
Name
m
ce
Sever
Condition
ity
s
Power
Major
The AC
phase
voltage of
A
phase A is
underv
greater
olt
than 50 V
and less
than the
low
voltage
alarm
threshold
when the
alarm
detection
delay
expires.
Power
Major
The AC
phase
voltage of
B
phase B is
underv
greater
olt
than 50 V
and less
than the
low
voltage
alarm
threshold
when the
alarm
detection
delay
expires.
Copyright © Huawei Technologies Co., Ltd.
7 System Operation and Maintenance
Possible Causes
1. The power supply
voltage is lower
than the power
overvolt alarm
thres.
2. If a voltage jumper
is used, possibly it
is incorrectly
connected.
3. If a toggle switch is
used, possibly it is
incorrectly set.
1. The power supply
voltage is lower
than the power
overvolt alarm
thres.
2. If a voltage jumper
is used, possibly it
is incorrectly
connected.
3. If a toggle switch is
used, possibly it is
incorrectly set.
Solutions
1. Check the
power supply
voltage.
2. Maintain or
replace the
voltage
jumper.
3. Correctly set
the toggle
switch.
1. Check the
power supply
voltage.
2. Maintain or
replace the
voltage
jumper.
3. Correctly set
the toggle
switch.
171