Check Item
Infrared
humidifier
Indoor fan
Compressor
Air filters
Connection
s of
internal
pipelines
Differential
pressure
sensor
Issue 12 (2020-10-28)
Expected Result
● The humidifier is secured.
● The protective device for the infrared humidifier is removed
(Corresponding to NetCol8000-A100).
● The fastener of the high water level detection switch is
removed.
● The high water level detection switch connects to the HWA
cable terminal.
● There is no foreign matter in the water pan.
● The automatic overfall gap is secured to the bottom of the
water pan.
● The indoor fan is lowered and secured to the bottom plate of
the cabinet.
● There is no foreign matter in the indoor fan.
● The sheet metal for transporting the compressor is removed.
● The bolts on the compressor are tightened.
The air filter is correctly installed according to the air flow
direction on the frame.
● The hose clamp and cable ties of the condensate water pipes
are secured.
● The pipes in the cooling system are secured.
● The cable ties on the differential pressure tubes are secured.
● There is no foreign matter in the differential pressure tubes.
The differential pressure tubes are not seriously bent.