5.7.4 Clearing the Runtime

Context
To clear the runtime of the smart cooling product component, log in as the Admin
or Engineer user.
Performance value clearance can be performed only after component
maintenance. Otherwise the component may run overtime and degrade
performance.
Procedure
Step 1 On the home screen, choose Maint > Performance Maint.
displayed.
Figure 5-41 Performance maint screen
Step 2 Tap Clear of a specific performance parameter to clear its runtime.
----End

5.7.5 Calibrating a Sensor

Context
Procedure
Step 1 On the home screen, choose Maint > Sensor Adjust.
Issue 12 (2020-10-28)
NO TICE
Calibrate a sensor if the displayed temperature or humidity on the sensor
deviates from the actual value. For example, if the return air temperature
measured by other temperature detection devices at the return air detection
point is 20°C while the value measured by the sensor is 22°C, the sensor has
an error of 2°C, and the calibration value should be set to –2°C.
To calibrate a sensor, log in as the Admin or Engineer user.