How Do I Clear Component Runtime - Huawei FusionCol8000-E240 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Step 2 You can tap an alarm to go to the Details screen of the alarm.
Figure 9-4 Alarm details
● If the
cleared. Such an alarm can be automatically cleared after the fault is rectified.
● If the
Such an alarm is manually cleared by tapping the Manually Clear icon after the fault is
rectified. The alarm clearance type varies with smart cooling products. Perform operations as
required.
Step 3 Tap Fault Diagnosis_Repair to view the diagnosis report. Rectify the faults by
following instructions in the diagnosis report.
Figure 9-5 Diagnosis report
----End
Follow-up Procedure
To query historical alarms, choose Common Function > Query Hist Alarms on
the home screen or choose Alarms > Query Hist Alarms on the home screen.

9.1.10 How Do I Clear Component Runtime?

Issue 02 (2021-04-15)
NO TE
icon is not displayed on the Details screen, the alarm can be automatically
icon is displayed on the Details screen, the alarm can be manually cleared.
NO TE
Historical alarms are displayed in chronological order. The latest cleared alarm is displayed
in the uppermost row.
Copyright © Huawei Technologies Co., Ltd.
9 FAQ
237