FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Locatio
Display Name
n
Hot aisle 4 temp/
humid
Hot aisle 5 temp/
humid
Hot aisle 6 temp/
humid
● The default T/H sensor address is 1.
● Keep the last RS485_R DIP switch at OFF.
● After the addresses are set, power on the device, choose Settings > System
Settings > T/H sensor on the home screen of the display module, and set the
sensors in the aisles corresponding to the addresses to Enable. Otherwise, the
sensors will not work.
----End
4.7 (Optional) Installing Electric Heater Components
and Cables
Electric heater components include the electric heating belt, temperature sensor
probe, and electric heater controller.
Procedure
Step 1 Remove the exhaust side panel.
Step 2 Install the electric heater controller.
Issue 02 (2021-04-15)
Addre
ss
24
25
26
NO TICE
Copyright © Huawei Technologies Co., Ltd.
DIP Switch No.
1
2
3
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
4 System Installation (FDC Scenario)
4
5
ON
ON
ON
ON
ON
ON
6
OFF
OFF
OFF