2.6 Technical Specifications

Table 2-5 General specifications
Item
Maximum power
Maximum
current
Total cooling
capacity
Sensible cooling
capacity
Sensible heat
ratio
System
dimensions (H x
W x D)
Installation
scenario
Power system
Air filter level on
the indoor air
return side (EN
779)
Air filter level on
the outdoor air
intake side (EN
779)
Fan type
Air volume
Net weight
Operating weight
Issue 02 (2021-04-15)
Specifications
(Building Scenario)
78.5 kW (default power)
140 A (default current)
1
240 kW
1
240 kW
100%
3600 mm x 2438
mm x 4700 mm
Indoor
380–415 V AC, 3-phase, 50 Hz/60 Hz
G4
G3
EC
Indoor: 55,000 m
Outdoor: 50,000 m
5000 kg
5500 kg
Copyright © Huawei Technologies Co., Ltd.
Specifications (FDC Scenario)
4150 mm x 2438 mm x 6058 mm
FDC
3
/h
3
/h
11,000 kg
11,500 kg