Operating Environment Specifications - Huawei FusionCol8000-E240 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Button
Button

2.5 Operating Environment Specifications

Environmental Specifications
Table 2-2 Environmental specifications
Item
Operating
temperature
Operating humidity
Storage temperature
Storage humidity
Altitude
Table 2-3 Derating coefficients
Altitude
(m)
Air volume
coefficient
Cooling
capacity
coefficient
Note: The sensible heat ratio is always 100%.
Issue 02 (2021-04-15)
Operation
When the
smart cooling
product is
shut down,
hold down
the button for
more than
10s.
Specifications
–40°C to +45°C
5%–95% RH
–40°C to +70°C
5%–95% RH
The performance is not derated when the altitude is
below 1000 m, and is derated when the altitude ranges
from 1000 m to 4000 m.
[0,100
1000
1500
0)
1
0.887
0.835
1
0.887
0.835
Copyright © Huawei Technologies Co., Ltd.
Function
A dialog box is displayed, asking you whether
to restore the factory settings.
200
2500
0
0.78
0.737
5
0.78
0.737
5
2 Product Description
3000
3500
4000
0.692
0.649
0.608
0.692
0.649
0.608
24

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fusioncol8000-e240h4

Table of Contents