Huawei FusionCol8000-E240 User Manual page 120

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Parameter
Enable
teamwork
CAN resistor
Teamwork
function
Networking
mode
Teamwork
parameter
synchronizati
on
Number of
systems in
this group
Number of
running
systems in
this group
Issue 02 (2021-04-15)
Description
Sets the status of each build-out
resistor of smart cooling products
in teamwork networking. This
parameter is available when the
CAN network mode is used.
Indicates whether to enable the
teamwork function. If no, the unit
operates independently. If yes, the
unit operates in a team with other
units.
Indicates the networking mode
for teamwork control. The
networking mode set on the
screen must be consistent with
the actual networking mode.
Otherwise, the teamwork control
function will be unavailable. If the
networking mode changes, select
the corresponding networking
mode on the screen.
If Teamwork function and
Teamwork parameter
synchronization are both set to
Enable, you can select Set Local
or Set Teamwork when setting
parameters.
Sets the number of smart cooling
products in a group. The value is
an integer ranging from 1 to 32.
Specifies the number of running
units in this group. The value is an
integer ranging from 1 to the
value of Number of systems in
this group.
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Setting Rule
● Set this parameter to No
for non-teamwork
scenarios.
● For teamwork control,
set this parameter to Yes
for the first and last
smart cooling products
in the network, and set
this parameter to No for
other smart cooling
products.
Set this parameter based
on onsite heat load
distribution.
Use CAN or FE networking
mode. CAN network refers
to CAN teamwork
networking.
CAN network indicates
teamwork control over a
CAN bus. FE network
indicates teamwork control
over an FE port.
● Set Local: Set
parameters for the local
unit.
● Set Teamwork: Set
parameters for all units
in a teamwork group.
Enter the total number of
smart cooling products in
the group.
The master unit assigns
operating machines in
ascending order of the
group address. The address
meets the 1-32
requirement. The remaining
units are automatically
classified as standby
devices.
111