FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
3.
4.
5.
Step 5 Tap the text box next to SNMP Port, set SNMP Port based on the actual port
number, tap
Issue 02 (2021-04-15)
NO TICE
Passwords of an authentication protocol and proprietary protocol must
comply with the following policies:
– The password must consist of 8–15 characters and contain at least two
types of characters among uppercase letters (A–Z), lowercase letters (a–z),
and digits (0–9).
– A password must be different from the corresponding user name or
inverted user name.
– A password must not be a string containing duplicate sections, such as
12a12a12a.
Set SHA password and Confirm Password and tap
Figure 6-15 Setting an SHA password
Set AES password and Confirm Password as planned.
Figure 6-16 Setting an AES password
Tap Submit.
, and tap Submit.
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
as planned.
121