FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
1.
2.
Figure 8-30 Refrigerant detection
Table 8-6 Mapping between temperatures and R410A saturation pressures
Temperatur
e (ºC)
0
1
2
3
4
5
6
7
8
9
10
11
12
Issue 02 (2021-04-15)
Dial the refrigerant vendor's hotline to confirm the refrigerant authenticity.
As shown in
Figure
8-30, place the refrigerant in an indoor place with
constant temperature and humidity for 24 hours. Then, use a thermometer to
measure the temperature of the refrigerant tank outer surface and connect a
pressure gauge to the pressure tank to measure the internal pressure. Find the
saturation pressure corresponding to the measured outer surface temperature
from
Table
8-6. If the deviation between the saturation pressure and the
measured internal pressure is greater than 0.2 MPa, the refrigerant does not
meet the requirements and needs to be replaced.
Saturation
Pressure –
Gauge
Pressure
(MPa)
0.7
0.73
0.75
0.78
0.81
0.84
0.87
0.9
0.93
0.96
0.99
1.02
1.05
Copyright © Huawei Technologies Co., Ltd.
Temperatu
Saturation
re (ºC)
Pressure –
Gauge
Pressure
(MPa)
19
1.31
20
1.35
21
1.39
22
1.43
23
1.47
24
1.51
25
1.56
26
1.60
27
1.65
28
1.69
29
1.74
30
1.79
31
1.84
8 System Maintenance
Temperatu
Saturatio
re (ºC)
n
Pressure –
Gauge
Pressure
(MPa)
38
2.21
39
2.27
40
2.33
41
2.39
42
2.45
43
2.51
44
2.57
45
2.63
46
2.7
47
2.76
48
2.83
49
2.9
50
2.97
212