Step 3 Open the outdoor intake air filter and take out the desiccant bag from the
outdoor air intake compartment.
Step 4 Open the maintenance door and water barrier of the spray pump, and take out
the two desiccant bags from the spray pump compartment.
Step 5 Loosen the three transport fixing bolts of the compressor using a 13# solid wrench
and remove the sheet metal fasteners.
Figure 3-18 Removing sheet metal fasteners from the compressor
Step 6 Tighten the bolts on the compressor again to a torque of 12 N·m.
Step 7 Install the adjustable side panels for the compressor.
----End

3.4 Installing Cables

3.4.1 Precautions

Issue 02 (2021-04-15)
NO TE
● Do not remove the bolts.
● Keep the removed sheet metal fasteners properly for future transportation.
Connections of all power cables, control cables, and ground cables must
comply with local electrical regulations, and the cable specifications should
comply with local cabling specifications.
For details about the maximum current, see the device nameplate.
Check that the input voltage and frequency of the primary power supply meet
the requirements.
Only trained and qualified personnel are allowed to connect cables.
Before connecting cables, use a multimeter to measure the input voltage and
ensure that the power supply is disconnected.
All smart cooling products must be securely grounded before being powered
on.