Huawei FusionCol8000-E240 User Manual page 133

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Context
On the main screen of the display module, there are Start and Shutdown buttons
for controlling the startup and shutdown of smart cooling products.
Prerequisites
Download the Service Expert app from HUAWEI AppGallery. The app can only run
on Android currently. You must apply for the permission to use the app after
downloading it.
Procedure
Step 1 Tap Start on the home screen of the display module.
Issue 02 (2021-04-15)
If the device is powered on again after a power failure, the device
automatically restores to the original startup/shutdown state before the
power failure.
Hardware ports are reserved on the display module to control the status of
remote dry contacts or remote startup and shutdown signals. The status of
remote dry contacts and remote startup and shutdown signals is started by
default.
Starting a unit over the screen or NMS is valid only when the status of remote
dry contacts or remote start/shutdown signal is started.
If you choose Settings > System Settings > System Control and set Require
password to start or shutdown onsite to Yes, a password is required for
startup or shutdown; if you set Require password to start or shutdown
onsite to No, no password is required for startup or shutdown verification.
If it is the first startup, tap Confirm. This indicates the initial startup after
power-on. Go to
Step 2
Figure 6-20 Initial startup screen
Copyright © Huawei Technologies Co., Ltd.
to perform the initial startup verification.
6 Power-On Commissioning
124