Pipe Support - Huawei FusionCol8000-E240 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Item
Water tank
drainpipe
Condensate
water pan
drainpipe
Floor drain
pipe

4.2.3 Pipe Support

Supports for pipes and water pipes as shown in the figure. The actual appearance
of the supports will be different based on onsite situations.
Figure 4-3 Pipe supports (unit: mm)
Issue 02 (2021-04-15)
Connector
G 1-1/2 inch
external
thread
connector
G 1 inch
external
thread
connector
-
NO TE
● The height of the U-shaped pipe clamp is 5 mm less than the pipe diameter (including
the thermal insulation foam).
● Install a support every 2500 mm for the straight sections of pipes, and 1000 mm away
from each bending point in turning sections.
Copyright © Huawei Technologies Co., Ltd.
4 System Installation (FDC Scenario)
Dimensions
Material
DN50
Rigid pipe (made of
PP-R, C-PVC, or
other materials)
DN32
Rigid pipe (made of
PP-R, C-PVC, or
other materials)
G50
Rubber hose
Descriptio
n
69

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fusioncol8000-e240h4

Table of Contents