FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Menu
Settings > Alarm
Settings >
Compressor
Settings > Alarm
Settings > Spray
System
Settings > System
Settings > Common
Settings
Issue 02 (2021-04-15)
Parameter
Compressor
liquid pipe
temp sensor
fault
Spray water
supply
abnormal
Spray drain
abnormal
Temperature
and
humidity
control type
Temperature
setpoint
Humidity
setpoint
Cold aisle
sensor*
Hot aisle
sensor*
Outdoor
intake air
sensor*
Copyright © Huawei Technologies Co., Ltd.
C Parameter Description
Description
● Enable: Alarms are reported to the
NMS. Active alarms are displayed on
the display module and the system
performs related protection actions.
● Disable: No alarms are generated and
no protection actions are performed.
● Enable: Alarms are reported to the
NMS. Active alarms are displayed on
the display module and the system
performs related protection actions.
● Disable: No alarms are generated and
no protection actions are performed.
● Enable: Alarms are reported to the
NMS. Active alarms are displayed on
the display module and the system
performs related protection actions.
● Disable: No alarms are generated and
no protection actions are performed.
This parameter can be set to Cold aisle,
Hot aisle, Return air, or Supply air
based on site requirements. The
temperature and humidity setpoints
corresponding to the selected control
mode are enabled.
After Temperature and humidity
control type and the temperature value
under this type are set, the device
performs cooling or heating based on the
settings.
After Temperature and humidity
control type and the humidity value
under this type are set, the device
performs humidifying or dehumidifying
based on the settings.
You can enable or disable the cold aisle
sensors.
You can enable or disable the hot aisle
sensors.
Outdoor intake air sensor* can be set to
Enable or Disable.