Replacing A Differential Pressure Switch (Fdc Scenario) - Huawei FusionCol8000-E240 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Step 4 Remove the pressure inlet tube.
Step 5 Remove the screws on the top cover of the differential pressure switch and cable
screws using a Phillips screwdriver and remove the cables.
Step 6 Remove the four screws using a Phillips screwdriver and remove the differential
pressure switch.
Step 7 Set a new value for the differential pressure switch based on the nearby label.
Step 8 Install the new differential pressure switch and sheet metal, install the pressure
inlet tube, and connect cables.
Step 9 Power on the device and tap Start on the home screen. Ensure that the device is
running properly without generating alarms.
----End

8.5.6 Replacing a Differential Pressure Switch (FDC Scenario)

Prerequisites
Context
The differential pressure switch can be maintained from the end only after the air
filter is removed.
Procedure
Step 1 On the home screen of the display module, tap Shutdown and turn off the device
switch in the PDF.
Exercise caution because the device is still energized after it is shut down on the
screen of the display module.
Step 2 Remove the outdoor intake air filter.
Step 3 Remove the bolts from the sheet metal fastener and push the baffle plate.
Issue 02 (2021-04-15)
NO TE
Record the port position of the removed pressure inlet tube. After the replacement is
complete, reinstall the tube to the original position.
A differential pressure switch needs to be replaced.
A spare differential pressure switch of the same model is available and
functional.
Tool: Phillips screwdriver
NO TICE
Copyright © Huawei Technologies Co., Ltd.
8 System Maintenance
193

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fusioncol8000-e240h4

Table of Contents