Replacing An Air Exhaust Ntc Temperature Sensor (Building Scenario) - Huawei FusionCol8000-E240 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Figure 8-15 Removing a T/H sensor
Step 5 Disconnect the cable from the T/H sensor.
Step 6 Slide and remove the T/H sensor.
Step 7 Install the new T/H sensor and reconnect the cable.
Before installing the new T/H sensor, check that its DIP switch settings are
consistent with the DIP switch settings of the old T/H sensor.
Step 8 Power on the device and tap Start on the home screen. Ensure that the device is
running properly without generating alarms.
----End
8.5.9 Replacing an Air Exhaust NTC Temperature Sensor
(Building Scenario)
Prerequisites
Issue 02 (2021-04-15)
NO TICE
An NTC temperature sensor needs to be replaced.
A spare NTC temperature sensor of the same model is available and
functional.
Tool: Phillips screwdriver
Copyright © Huawei Technologies Co., Ltd.
8 System Maintenance
198