How Do I Calibrate A T/H Sensor; How Do I Check The Display Of Normal Air Volume - Huawei FusionCol8000-E240 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Context
Performance value clearance can only be performed after component
maintenance. Otherwise, the component may run overtime and weaken
performance.
Procedure
Step 1 On the home screen, choose Maint > Performance Maint.
Step 2 Tap Clear in the row of a performance parameter to clear the runtime.
----End

9.1.11 How Do I Calibrate a T/H Sensor?

Context
Calibrate a sensor if the displayed temperature or humidity values on the sensor
deviate from the actual values. For example, if the return air temperature
measured by other temperature detection device at the return air detection point
is 20°C while the sensor measured 22°C, the sensor has an error of 2°C, and the
calibration value can be set to –2°C.
Procedure
Step 1 Choose Maint > Sensor Calibration on the home screen.
Step 2 Fill the calibration value based on the measured error.
----End

9.1.12 How Do I Check the Display of Normal Air Volume?

Prerequisites
Tool: differential pressure gauge (purchased onsite)
Procedure
Step 1 Tap Shutdown on the home screen of the display module.
Step 2 Open the side panel of the unit.
Issue 02 (2021-04-15)
NO TICE
NO TE
Exercise caution because the device is still energized after it is shut down on the screen of
the display module.
Copyright © Huawei Technologies Co., Ltd.
9 FAQ
238