Table 3-5 Cable terminal requirements
Port
Active input
Standby
input
3.3 Installing a FusionCol8000-E
3.3.1 Unpacking and Checking
Procedure
Step 1 Verify that the package is intact. If any damage is found, notify the carrier
immediately.
Step 2 Remove the plastic packaging materials.
Step 3 Check the types and quantity of fittings according to the fitting list. If any fitting is
missing, contact Huawei technical support.
----End
3.3.2 Securing a Smart Cooling Product
Prerequisites
The evenness of concrete platforms is critical to device installation. Ensure that the
height (altitude) difference between platforms does not exceed 5 mm.
Issue 02 (2021-04-15)
Connection
Method
Crimped DT
terminals
Crimped DT
terminals
NO TICE
Copyright © Huawei Technologies Co., Ltd.
3 System Installation (Building Scenario)
Bolt
Torque
Specificatio
ns
M10
20 N·m
M10
20 N·m
Remarks
Standard
configuratio
n, delivered
with the
product.
Standard
configuratio
n, delivered
with the
product.
37