Huawei FusionCol8000-E240 User Manual page 208

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Procedure
Step 1 On the home screen of the display module, tap Shutdown and turn off the device
switch in the PDF.
Exercise caution because the device is still energized after it is shut down on the
screen of the display module.
Step 2 Open the adjustable side panel.
Step 3 Remove the sealing plate from the exhaust fan.
Figure 8-16 Removing the sealing plate from the exhaust fan
Step 4 Cut off the cable ties and remove the screws that secure the NTC temperature
sensor.
Step 5 Remove the interconnection terminal from the cable of the NTC temperature
sensor.
Step 6 Install the new NTC temperature sensor, reconnect the cables, and secure the NTC
temperature sensor in the original position.
Step 7 Bind the cable ties.
Step 8 Power on the device and tap Start on the home screen. Ensure that the device is
running properly without generating alarms.
----End