8.2 Routine Maintenance

Smart Cooling Product Running
Smart Cooling Product Maintenance
The installation and maintenance of the smart cooling product must be
periodically performed by trained personnel to ensure personal safety. Take
insulation measures for tools and human bodies before operating the smart
cooling product. Do not insert your fingers or tools into the operating fan. Wait
until the fan stops running. Before entering the device, ensure that electrical
devices are physically isolated from the general power supply.
Issue 02 (2021-04-15)
Exercise caution during professional maintenance. For details, contact Huawei
technical support.
When replacing a component, do not lean the component against the
cabinet.
Softened water is used for circulation in the water tank in summer. The water
quality should meet the requirements.
The circulation water system is full of water in summer. When the device is
not used in winter, drain the water from the water pan and pipes to avoid
freezing.
When a fan of the unit is faulty, shut down the fan immediately for repair. If
the fan cannot be repaired within two hours, use a baffle plate to block the
air vent after removing the fan to prevent air backflow.
After installing the smart cooling product, if the construction company is still
in the process of construction, take protective measures to prevent sundries
and dust from falling into the smart cooling product.
It is recommended that the following maintenance items be performed every
three to six months. The actual maintenance period depends on the loads and
surrounding conditions.
Check the tightness of the bolts.
Check the sealing strip of the maintenance door and the flexible
connector of the air duct. If there is any air leakage, replace them in time.
It is recommended that the following maintenance items be performed once a
year.
Check electrical cable connections.
Check whether the shell of the smart cooling product is damaged or
corroded. If yes, clean the shell and take anti-corrosion measures.
Check whether the gap between the impeller and the flow deflecting ring of
the fan is even, to prevent the impeller from colliding with the flow deflecting
ring.
After the smart cooling product stops working in cold areas or winter, close
the exhaust, supply, and return air dampers, and drain water from the
circulation water system.