FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Procedure
Step 1 (LAN settings) On the home screen, choose Settings > Comm Settings > LAN IP
Settings and set LAN IP address assignment mode to Manual. Set LAN IP
address, LAN subnet mask, and LAN gateway based on the actual plan.
Figure 6-8 LAN IP Settings
Step 2 (WAN settings) On the home screen, choose Settings > Comm Settings > WAN
IP Settings, and set the IP address, subnet mask, and gateway based on the actual
plan.
Figure 6-9 WAN IP Settings
Step 3 On the home screen, choose Settings > Comm Settings > Modbus Settings and
set Link mode to Server and client or Client. Set Client encryption to Enable.
Issue 02 (2021-04-15)
NO TE
● If the DHCP server is configured on the NMS, select DHCP auto. If no, set this
parameter to Manual.
● The LAN IP address must be in the 192.168.248.X network segment.
NO TE
The WAN IP address cannot be in the 192.168.245.X, 192.168.246.X, or 192.168.248.X
network segment.