Huawei FusionCol8000-E240 User Manual page 231

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Context
Before checking and maintaining the device, ensure that the primary power supply
to the device is disconnected and the drive has been powered off for 10 minutes.
Otherwise, electrical shocks may occur.
Procedure
Step 1 On the home screen of the display module, tap Shutdown and turn off the device
switch in the PDF.
Exercise caution because the device is still energized after it is shut down on the
screen of the display module.
Step 2 Remove the adjustable side panels for the compressor drive.
Step 3 Remove all cables from the drive and cut the cable ties using diagonal pliers.
Step 4 Remove the four screws on the drive using a Phillips screwdriver, and pull out the
drive.
Figure 8-37 Removing a drive
Step 5 Install the new drive.
Step 6 Connect the cables to the drive.
Step 7 Install the adjustable side panels.
Step 8 Power on the smart cooling product, and choose Maint > Wizard Startup on the
home screen. Start the compressor and check that the compressor works properly
Issue 02 (2021-04-15)