FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Step 4 Install the new filter dryer.
● When welding a new filter dryer, identify the arrow on the filter dryer. The
arrow direction should be the same as the refrigerant flow direction.
● Do not use face-down bonding when welding.
1.
2.
3.
Step 5 Perform a leakage test with nitrogen.
Step 6 After checking that the smart cooling product does not leak, vacuumize the smart
cooling product and fill the refrigerant.
Step 7 Power on the device and tap Start on the home screen. Ensure that the smart
cooling product is running normally without any alarms.
----End
8.5.17 Replacing a Compressor Drive
Prerequisites
●
●
●
Issue 02 (2021-04-15)
NO TICE
Remove the rubber plug from the port of the filter dryer.
Install the filter dryer in the unit and weld copper pipes at both ends.
Reinstall the hold hoop.
Figure 8-36 Installing the filter dryer
A drive needs to be replaced.
A spare drive of the same model is available and functional.
Tools: Phillips screwdriver, diagonal pliers, cable tie
Copyright © Huawei Technologies Co., Ltd.
8 System Maintenance
221