Operating Specifications
Table 2-4 Operating specifications
Item
Operating temperature
Operating humidity
Temperature of inlet
chilled water (or glycol)
Storage temperature
Storage humidity
Altitude
Temperature
adjustment range
Temperature
adjustment precision
Humidity adjustment
range
Humidity adjustment
precision

2.6 Technical Specifications

Table 2-5 Downflow smart cooling product specifications
Parameter
Power system
Cooling capacity
(kW)
Maximum
current (cooling
only/full
configuration)
Number of fans
Issue 02 (2020-08-30)
NetCol8000-C070
4–45°C
20%–80% RH
4–20°C
–40°C to +70°C
5%–95% RH (non-condensing)
0–4000 m (derated when the altitude is in the range
of 1000–4000 m)
15–45°C
1°C
20%–80% RH
5% RH
NetCol8000-
C070D
380–415V AC, 3PH, 50/60Hz Dual route
60.1
1
7.3A/16.5A
1
Copyright © Huawei Technologies Co., Ltd.
NetCol8000-
C130
NetCol8000-
NetCol8000-
C130D
C190D
118.8
182.9
14A/32.3A
20.7A/39A
2
3