Huawei NetCol8000-C070 User Manual page 43

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Application
Scenario
Network
cable for
teamwork
Table 3-6 Description about the cables of the NetCol8000-C130/NetCol8000-C190
Applicat
ion
Scenario
Indoor
unit
Issue 02 (2020-08-30)
Name
Cord end
terminal of
power cables
(with heating
and
humidification
)
Standard
network cable
(standard
configuration)
Name
Technical Requirements
Power cable
Electrical power cable, 600
(without
V/1000 V, ZA-RVV, 5 x 4
heating and
mm
humidification)
wires: red, yellow, green,
blue, black), 32A, outdoor
cable, CE
Power cable
Electrical power cable, 600
(with heating
V/1000 V, ZA-RVV, 5 x 6
and
mm
humidification)
wires: red, yellow, green,
blue, black), 32A, outdoor
cable, CE
OT terminal of
Naked crimping terminal:
power cables
OT, 6 mm
plating, 12–10 AWG
Copyright © Huawei Technologies Co., Ltd.
Technical
Requirements
Naked crimping
terminal, single-wire
cord end terminal, 4
2
mm
, 20 A, tin
plating, insertion
depth 12 mm
Signal cable,
shielded straight-
through cable, 10 m,
MP8-II,
CC4P0.5GY(S), MP8-
II, FTP
2
, black (five core
2
, black (five core
2
, M6, 50 A, tin
3 Installation Guide
Remarks
Delivered with the
fittings
1 PCS (10 m)
Remarks
The length is
determined by site
survey.
Do not install the
neutral wire (blue).
Cut it off and wrap it
securely using
insulation tape
onsite.
The length is
determined by site
survey.
Do not install the
neutral wire (blue).
Cut it off and wrap it
securely using
insulation tape
onsite.
Delivered with the
fittings
35

Advertisement