NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
If the water inlet temperature exceeds 10°C or the total load is less than 30% of
the cooling capacity of a single smart cooling product, the humidity may be high.
The customer is advised to add a dehumidifier (engineering procurement).
Pipe Dimensions
The following table lists the reserved pipe dimensions of a NetCol8000-C.
Table 2-2 Pipe dimensions
Item
Water outlet pipe
Water inlet pipe
Humidifier water inlet pipe
Drainpipe
Installation Requirements
Table 2-3 Installation requirements
Item
Door
Floor
Pipe routing
Maintenance distance
Power distribution requirements
Issue 02 (2020-08-30)
NO TICE
Copyright © Huawei Technologies Co., Ltd.
Specifications
G 2 inch port with inner threads
G 2 inch port with inner threads
G 1/2 inch port with outer threads
BSPP 3/4 inch port with inner threads
Specifications
Width ≥ 1.3 m; height ≥ 2.3 m; turning
radius ≥ 3.2 m
Floor bearing capacity ≥ 400 kg/m
Upflow: left pipe routing,and left and
bottom pipe routing
Downflow: left and bottom pipe
routing
Front maintenance distance ≥ 900 mm
Leakage circuit breakers are not
recommended for the active power
supply route. If a leakage circuit
breaker is required by the customer or
local regulations, select the residual
current circuit breaker (RCCB) that is
insensitive to single-phase DC
pulsation and transient impulse
current.
2 Product Overview
2
23