Huawei NetCol8000-C070 User Manual page 225

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Menu
Issue 02 (2020-08-30)
Name
Humidity
setpoint
Return-air sensor
Cold aisle sensor
Hot aisle sensor
Heating function
Copyright © Huawei Technologies Co., Ltd.
Parameter Description
After the Temperature and
humidity control type and
the humidity value under
this type are set, the device
conducts humidifying or
dehumidifying based on
the settings.
The sensors on the return
air side are set to Enable.
The sensors in cold aisles
can be set to Enable or
Disable.
The sensors in hot aisles
can be set to Enable or
Disable.
Enable indicates that the
electric heater will be
started when the ambient
temperature is lower than
the certain temperature
range of the temperature
set point. Disable indicates
that the electric heater will
not be started. Enabled
when active power
indicates that the electric
heater will be started when
the main power is active
and the ambient
temperature is lower than
the certain temperature
range of the temperature
set point.
D Parameter Description
Default Value
50.0 %RH
Enable the
corresponding
humidity and
temperature
sensor installed
on the return
air side.
Disable
Disable
Enabled when
active power
217