NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Parameter
Number of
running
smart
cooling
products in
this group
Rotation
function
Rotation
period
Rotation
time
Forced
rotation
Issue 02 (2020-08-30)
Description
Number of active
units in a group. The
value ranges from 1
to Number of smart
cooling products in
this group.
Disable or enable the
active and standby
smart cooling
products to change
identity after a certain
time, maximizing their
service life.
Rotation days (1–30).
24 hours in a day (0–
23).
Forced rotation
specifies whether to
enable a forcible
rotation on the group
before the specified
rotation time. After a
forced rotation, the
accumulated time is
recalculated.
Copyright © Huawei Technologies Co., Ltd.
Configuration
Principle
The host allocates
running units by smart
cooling product unit
address in ascending
order, which is from 1
to 32. The rest will
become the standby
ones.
This function is
recommended when
the heat is even.
7 by default
0 by default
This item is set to No
by default. If forced
rotation is required, the
function is set to Yes.
4 Commissioning
Default
Value
2
Disable
7 day (s)
0
No