Huawei NetCol8000-C070 User Manual page 91

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Menu
Issue 02 (2020-08-30)
Paramete
Description
r
Humidifyi
The humidifying function
ng
can be set to Enable,
function
Disable, or Enabled
when active power.
Dehumidif
The dehumidifying
ying
function can be set to
function
Enable, Disable, or
Enabled when active
power.
Floor
Based on site, set the
water
device action to
overflow
Shutdow, Inactivity,
alarm
Only indoor fan
action
running, or
Humidification stopped
after the floor overflows.
Copyright © Huawei Technologies Co., Ltd.
4 Commissioning
Configuration Principle
Enable indicates that the
electric humidifier will be
started when the ambient
humidity is lower than the
certain humidity range of
the humidity set point.
Disable indicates that the
electric humidifier will not
be started. Enabled when
active power indicates
that the electric humidifier
will be started when the
main power is active and
the ambient humidity is
lower than the certain
humidity range of the
humidity set point.
Enable indicates that the
dehumidification function
will be enabled when the
ambient humidity exceeds
the certain humidity range
of the humidity set point.
Disable indicates that the
dehumidification function
will not be enabled.
Enabled when active
power indicates that the
dehumidification function
will be enabled when the
main power is active and
the ambient humidity
exceeds the certain
humidity range of the
humidity set point.
Retain the default value.
83

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol8000-c130Netcol8000-c190

Table of Contents