NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Alar
m ID
A193
A200
A208
Issue 02 (2020-08-30)
Alarm
Alarm
Possible Cause
Name
Severi
ty
Air-side
Major
1. The differential
diff
pressure sensor cable is
pressure
loose or damaged.
sensor
2. The pressure tube of
fault
the differential pressure
sensor is reversely
connected.
3. The differential
pressure sensor is faulty.
Indoor
Major
1. The communications
fan 1
cable to the fan is not
communi
connected properly.
cation
2. The fan is faulty.
failed
Indoor
Major
1. The communications
fan 2
cable to the fan is not
communi
connected properly.
cation
2. The fan is faulty.
failed
Indoor
Major
1. The communications
fan 3
cable to the fan is not
communi
connected properly.
cation
2. The fan is faulty.
failed
Indoor
Major
1. The fan blade is stuck.
fan 1
2. The fan is faulty.
blocked
alarm
Indoor
Major
1. The fan blade is stuck.
fan 2
2. The fan is faulty.
blocked
alarm
Indoor
Major
1. The fan blade is stuck.
fan 3
2. The fan is faulty.
blocked
alarm
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Solution
1. Check the cable
connection to the
differential pressure
sensor.
2. Check the tube
connection to the
differential pressure
sensor.
3. Maintain or replace
the differential
pressure sensor.
1. Check the
communications cable
connection to the fan.
2. Maintain or replace
the fan.
1. Check the
communications cable
connection to the fan.
2. Maintain or replace
the fan.
1. Check the
communications cable
connection to the fan.
2. Maintain or replace
the fan.
1. Clear the blockage.
2. Maintain or replace
the fan.
1. Clear the blockage.
2. Maintain or replace
the fan.
1. Clear the blockage.
2. Maintain or replace
the fan.
145