Huawei NetCol8000-C070 User Manual page 220

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Menu
Settings >
T/H sensor
Settings >
Alarm
Settings >
Mainboard
Issue 02 (2020-08-30)
Name
Supply air low
temperature
alarm
Return air high
temperature
alarm
Return air low
temperature
alarm
Cold aisle high
temperature
alarm
Cold aisle low
temperature
alarm
Hot aisle high
temperature
alarm
Hot aisle low
temperature
alarm
High humidity
alarm
Low humidity
alarm
Return air filter
blocked alarm
Copyright © Huawei Technologies Co., Ltd.
Parameter Description
Specifies the alarm
threshold for a certain
alarm.
Specifies the alarm
threshold for a certain
alarm.
Specifies the alarm
threshold for a certain
alarm.
Specifies the alarm
threshold for a certain
alarm.
Specifies the alarm
threshold for a certain
alarm.
Specifies the alarm
threshold for a certain
alarm.
Specifies the alarm
threshold for a certain
alarm.
Specifies the alarm
threshold for a certain
alarm.
Specifies the alarm
threshold for a certain
alarm.
● Enable: Alarms are
reported to the EMS.
The LCD displays active
alarms and the system
implements related
protection actions.
● Disable: Alarms are not
reported and no
protection actions are
implemented.
D Parameter Description
Default Value
5.0 °C
45.0 °C
15.0 °C
40.0 °C
10.0 °C
45.0 °C
15.0 °C
85.0 %RH
20.0 %RH
Enable
212

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol8000-c130Netcol8000-c190

Table of Contents