4.5 Initial Configuration

4.5.1 Setting Temperature and Humidity Values and Enabling
T/H Sensors
Prerequisites
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H sensor.
Step 2 Set Return air sensor 2 to Enable.
Issue 02 (2020-08-30)
Running
Checks the component status, system parameters, and the name, control and
operating status, and other related information of the components in the
current smart cooling product system.
Alarms
Checks the active and historical alarms of the smart cooling product, and
deletes the historical alarms.
Settings
Sets the involved parameters for the operation of the smart cooling product.
Maint
Checks or deletes the logs or component total runtime/run factor, manually
diagnoses each component, calibrates the sensor and touch screen, exports
data, and upgrades the system.
About
Checks the model, manufacturer, monitoring version, detail version
information, and electronic label of the ACC.
The T/H sensors outside the cabinet need to be enabled when they are
installed, otherwise, skip
If you need to enable a humidity and temperature sensor, log in as the admin
user.
This section describes how to enable Cold aisle sensor 1.