NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Menu
Settings >
System
Settings >
Humidifier
Settings >
System
Settings >
Cooling cap.
mgmt
Maint >
Performance
Maint
Issue 02 (2020-08-30)
Name
Direct free-
cooling
-
Cooling capacity
management
function
Chilled water
valve total
runtime
Indoor fan total
runtime
Copyright © Huawei Technologies Co., Ltd.
Parameter Description
Set the parameters for the
direct free-cooling plenum
based on the actual
configurations of the
customer's direct free-
cooling module onsite and
the enabling and disabling
requirements of the direct
free-cooling function.
-
The cooling capacity
management function can
be set to Enable or
Disable.
Total runtime for chilled
water valve.
Total runtime for indoor
fan.
D Parameter Description
Default Value
● There is no
direct free-
cooling
function by
default.
Select No
when no
direct free-
cooling
plenum is
configured.
● Select
Enable
when a
direct free-
cooling
plenum is
configured
and needs
to be
enabled.
● Select
Disable
when a
direct free-
cooling
plenum is
configured
but need
not be
enabled.
-
Disable
0 h
0 h
225