Optional) Connecting The Direct Free-Cooling Plenum - Huawei NetCol8000-C070 User Manual

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Step 2 Set the DIP switches of T/H sensors.
for T/H sensors.
Table 3-10 DIP switch setting on a T/H sensor
Locati
on
Air
return
side
Cold
aisle
Hot
aisle
Direct
ventila
tion
● The default addresses of T/H sensors purchased from Huawei are 1.
● After the addresses are set, power on the device. On the LCD home screen,
choose Settings > System Settings > T/H Sensor, and set the sensors in the
aisles corresponding to the addresses to Enable. Otherwise, the sensors will not
work.
----End

3.6.9 (Optional) Connecting the Direct free-cooling plenum

Issue 02 (2020-08-30)
Display Name
Air return T/H
sensor 1
Cold aisle T/H
sensor 1
Cold aisle T/H
sensor 2
Cold aisle T/H
sensor 3
Hot aisle T/H
sensor 1
Hot aisle T/H
sensor 2
Hot aisle T/H
sensor 3
Fresh air
temperature
and humidity
Temperature
and humidity
at the return
air valve
NO TICE
Copyright © Huawei Technologies Co., Ltd.
Table 3-10
shows how to set the DIP switches
Addr
DIP Switch Sequence No.
ess
1
2
1
ON
OFF
11
ON
ON
12
OFF
OFF
13
ON
OFF
21
ON
OFF
22
OFF
ON
23
ON
ON
29
ON
OFF
27
ON
ON
3 Installation Guide
3
4
5
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
ON
ON
OFF
ON
ON
6
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
68

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol8000-c130Netcol8000-c190

Table of Contents