NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Menu
T/H
sensor
Issue 02 (2020-08-30)
Paramete
Description
r
In-cabinet
Based on site, set the
water
device action to
overflow
Shutdown, Inactivity,
alarm
Only indoor fan
action
running, or
Humidification stopped
after the floor overflows.
Temperatu
Cold aisle, Hot aisle,
re and
Return air, or Supply air
humidity
can be set as required.
control
The temperature and
type
humidity set points
correspond to the
selected control type can
be set.
Temperatu
After the Temperature
re setpoint
and humidity control type
and the temperature
value under this type are
set, the device conducts
cooling or heating based
on the settings.
Humidity
After the Temperature
setpoint
and humidity control type
and the humidity value
under this type are set,
the device conducts
humidifying or
dehumidifying based on
the settings.
Copyright © Huawei Technologies Co., Ltd.
4 Commissioning
Configuration Principle
Retain the default value.
● When the application
scenario is cold or hot
aisle containment, you
are advised to choose
Cold aisle if the cold
aisle T/H sensors are
configured, and choose
Supply air if the cold
aisle T/H sensors are
not configured.
● When the application
scenario is non-aisle
containment, you are
advised to choose
Return air, and choose
Cold aisle if the cold
aisle T/H sensors are
configured.
● Hot aisle is not
recommended.
Set this parameter as
required.
● Return air temperature:
26–35°C recommended
● Supply air temperature:
18–24°C recommended
● Cold aisle temperature:
18–24°C recommended
● Hot aisle temperature:
26–35°C recommended
Set this parameter as
required.
40%–60% RH
recommended