Table 3-5 Description about the cables of the NetCol8000-C070
Application
Scenario
Indoor unit
Issue 02 (2020-08-30)
Name
Power cable
(without
heating and
humidification
)
Power cable
(with heating
and
humidification
)
OT terminal
of power
cables
(without
heating and
humidification
)
OT terminal
of power
cables (with
heating and
humidification
)
Cord end
terminal of
power cables
(without
heating and
humidification
)
Copyright © Huawei Technologies Co., Ltd.
Technical
Requirements
Electrical power
cable, 600 V/1000 V,
ZA-RVV, 5 x 2.5
2
mm
, black (five
core wires: red,
yellow, green, blue,
black), 27 A, outdoor
cable, CE
Electrical power
cable, 600 V/1000 V,
2
ZA-RVV, 5 x 4 mm
,
black (five core
wires: red, yellow,
green, blue, black),
27 A, outdoor cable,
CE
Naked crimping
terminal: OT, 2.5
2
mm
, M6, 27 A, tin
plating, 16–14 AWG
Naked crimping
2
terminal: OT, 6 mm
,
M6, 50 A, tin plating,
12–10 AWG
Naked crimping
terminal, single-wire
cord end terminal,
2
2.5 mm
, 12.5 A, tin
plating, insertion
depth 12 mm
3 Installation Guide
Remarks
The length is
determined based on
site survey.
The neutral wire is not
required for the power
input to the smart
cooling product. Cut the
blue neutral wire onsite
and wrap the exposed
part using PVC
insulation tape.
The length is
determined based on
site survey.
The neutral wire is not
required for the power
input to the smart
cooling product. Cut the
blue neutral wire onsite
and wrap the exposed
part using PVC
insulation tape.
Delivered with the
fittings
Delivered with the
fittings
Delivered with the
fittings
34