Huawei NetCol8000-C070 User Manual page 187

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Figure 6-31 Removing the fan maintenance baffle plate
Step 4 After the electric heater cools to the room temperature, cut off the cable tie on
the electric heater cable and disconnect the interconnection terminal.
Step 5 Remove the four bolts from both ends of the electric heater and take out the
electric heater.
Figure 6-32 Removing an electric heater
Step 6 Install and secure the new electric heater by perform
maintenance baffle and close the front door.
Step 7 On the home screen, choose Maint > Wizard Startup, and commissing the
electric heater to check that the heater is normal. Then exit from the wizard
startup mode.
Step 8 On the home screen, choose Maint > Performance Maint to enter the
performance maintenance screen and clear the runtime of the electric heater.
----End