NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Alar
m ID
Issue 02 (2020-08-30)
Alarm
Alarm
Possible Cause
Name
Severi
ty
Return
Major
1. The cables to the
air 2
temperature and
temp/
humidity sensor are loose
humid
or damaged.
sensor
2. The DIP switch of the
comm
temperature and
failed
humidity sensor is set
incorrectly.
3. The temperature and
humidity sensor is faulty.
4. The communications
port of the main control
board is faulty.
Return
Major
1. The cables to the
air 3
temperature and
temp/
humidity sensor are loose
humid
or damaged.
sensor
2. The DIP switch of the
comm
temperature and
failed
humidity sensor is set
incorrectly.
3. The temperature and
humidity sensor is faulty.
4. The communications
port of the main control
board is faulty.
Cold aisle
Major
1. The cables to the
1 temp/
temperature and
humid
humidity sensor are loose
sensor
or damaged.
comm
2. The DIP switch of the
failed
temperature and
humidity sensor is set
incorrectly.
3. The temperature and
humidity sensor is faulty.
4. The communications
port of the main control
board is faulty.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Solution
1. Check the cables to
the temperature and
humidity sensor.
2. Set the DIP switch of
the temperature and
humidity sensor
correctly.
3. Maintain or replace
the temperature and
humidity sensor.
4. Maintain or replace
the main control
board.
1. Check the cables to
the temperature and
humidity sensor.
2. Set the DIP switch of
the temperature and
humidity sensor
correctly.
3. Maintain or replace
the temperature and
humidity sensor.
4. Maintain or replace
the main control
board.
1. Check the cables to
the temperature and
humidity sensor.
2. Set the DIP switch of
the temperature and
humidity sensor
correctly.
3. Maintain or replace
the temperature and
humidity sensor.
4. Maintain or replace
the main control
board.
131