Huawei NetCol8000-C070 User Manual page 103

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Parameter
Requirement
control
Issue 02 (2020-08-30)
Description
Enable or disable the
requirement control
for the master device.
● When the
requirement
control is Disable,
the master device
does not
synchronize data to
the slave device,
and all the smart
cooling products
operate based on
their own
requirements, not
referring to the
mode delivered by
the master device.
● When the
requirement
control is Anti-
competitive
running, the
master device
synchronizes data
(the temperature
and humidity
control type and
set points of the
master device and
other parameters)
to the slave device,
and all the smart
cooling products in
the group refer to
the mode delivered
by the master
device.
● When the
requirement
control is Indoor
fan unified
control, all smart
cooling product
fans in the group
rotate at the same
speed.
Copyright © Huawei Technologies Co., Ltd.
Configuration
Principle
Anti-competitive
running is
recommended for the
following scenario: In
one teamwork, the
temperature and
humidity control type
and temperature and
humidity set point of
units are the same, and
device heat loads are
distributed evenly.
4 Commissioning
Default
Value
Disable
95