Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Alar
m ID
A049
Issue 02 (2020-08-30)
Alarm
Alarm
Possible Cause
Name
Severi
ty
Supply
Warni
1. The temperature
air low
ng
sensors or temperature
temperat
and humidity sensors are
ure
located in inappropriate
alarm
positions.
2. The thermal load
power is low.
3. The ambient
temperature is below the
lower threshold.
4. The low temperature
alarm threshold is
inappropriate.
5. The value detected by
the temperature sensor
or temperature and
humidity sensor is
different from the actual
value.
6. The air filters are
blocked.
7. The chilled water valve
is stuck or faulty.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Solution
1. Adjust the positions
of the temperature
sensors or temperature
and humidity sensors.
2. Contact Huawei
technical support.
3. Measure the
ambient temperature.
Check whether other
causes exist if the
alarm persists in a long
time after startup.
4. Adjust the low
temperature alarm
threshold.
5. Calibrate or replace
the temperature sensor
or temperature and
humidity sensor.
6. Maintain or replace
the air filters.
7. Maintain or replace
the chilled water valve.
138