Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Menu
Issue 02 (2020-08-30)
Name
Return air temp
to forcibly start
cooling
Cold aisle temp
to forcibly start
cooling
DO association
Cooling capacity
management
function
Copyright © Huawei Technologies Co., Ltd.
Parameter Description
Specifies the temperature
threshold for forcibly
starting the compressor
when the return air
temperature is higher than
the threshold.
Specifies the temperature
threshold for forcibly
starting the compressor
when the cold air
temperature is higher than
the threshold.
● When DO associated
alarm is set to Smoke &
Water only, if a smoke
sensor alarm or water
overflow alarm is
generated, port 1 for
reporting common
alarms generates a dry
contact close alarm, and
port 2 for reporting
common alarms does
not function.
● When DO associated
alarm is set to Critical
& Major alarm, if a
critical alarm is
generated, port 1 for
reporting common
alarms generates a dry
contact close alarm; if a
major alarm is
generated, port 2 for
reporting common
alarms generates a dry
contact close alarm.
● When DO associated
alarm is set to No, ports
1 and 2 for reporting
common alarms are
open and generate no
alarms.
The cooling capacity
management function can
be set to Enable or
Disable.
D Parameter Description
Default Value
43.0 °C
27.0 °C
Smoke &
Water only
Disable
222