Huawei NetCol8000-C070 User Manual page 145

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Alar
m ID
A048
Issue 02 (2020-08-30)
Alarm
Alarm
Possible Cause
Name
Severi
ty
Supply
Critica
1. The temperature
air high
l
sensors or temperature
temperat
and humidity sensors are
ure
located in inappropriate
alarm
positions.
2. The thermal load
power is high or the
cooling capacity is
insufficient.
3. The ambient
temperature exceeds the
upper threshold.
4. The high temperature
alarm threshold is
inappropriate.
5. The value detected by
the temperature sensor
or temperature and
humidity sensor is
different from the actual
value.
6. The chilled water flow
is insufficient, or the
supply water temperature
is high.
7. The chilled water valve
is stuck or faulty.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Solution
1. Adjust the positions
of the temperature
sensors or temperature
and humidity sensors.
2. Add air conditioners
or contact Huawei
technical support.
3. Measure the
ambient temperature.
Check whether other
causes exist if the
alarm persists in a long
time after startup.
4. Adjust the high
temperature alarm
threshold.
5. Calibrate or replace
the temperature sensor
or temperature and
humidity sensor.
6. Check the pressure
and temperature of
chilled water.
7. Maintain or replace
the chilled water valve.
137