Installation Guide; Installation Precautions; Precautions - Huawei NetCol8000-C070 User Manual

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual

3.1 Installation Precautions

3.1.1 Precautions

To ensure the optimal operating condition and longest service life, install the
NetCol8000-C correctly as required.
Precautions
Layout Requirements
Issue 02 (2020-08-30)
Install the NetCol8000-C according to the design drawing and reserve space
for maintenance.
The pipes only can be routed from the bottom of the downflow units, the
NetCol8000-C must be installed in the equipment room with a raised floor.
The pipes can be routed from the side of the upflow units, the NetCol8000-C
can be directly placed on the concrete floor of the equipment room or secured
on the base.
The pipes can be routed from the bottom of the upflow units, the
NetCol8000-C can be only secured on the base.
Take appropriate thermal insulation and antifreeze measures for outdoor
water pipes to avoid poor drainage and insufficient water supply caused by
freezing.
When installing, seal the top of the NetCol8000-C by using a baffle or plastic
bag to prevent dust entering.
Check whether the environment meets the requirements before installation,
and whether reconstruction is required for routing water pipes and cables and
constructing ventilation pipes.
The equipment room should have good heat insulation, and the walls and
floor should be protected against moisture.
To ensure good ventilation, do not place the smart cooling product in the
corner of a room or at the end of a long and narrow room.
Copyright © Huawei Technologies Co., Ltd.
3

Installation Guide

3 Installation Guide
26