Modbus Management Support; Modbus Function Codes - Siemens RUGGEDCOM ROS v4.3 User Manual

Table of Contents

Advertisement

Chapter 1
Introduction
Section 1.8

ModBus Management Support

Modbus management support in RUGGEDCOM devices provides a simple interface for retrieving basic status
information. ModBus support simplifies the job of SCADA (Supervisory Control and Data Acquisition) system
integrators by providing familiar protocols for retrieving RUGGEDCOM device information. ModBus provides
mostly read-only status information, but there are some writable registers for operator commands.
The ModBus protocol PDU (Protocol Data Unit) format is as follows:
Function Code
CONTENTS
Section 1.8.1, "ModBus Function Codes"
Section 1.8.2, "ModBus Memory Map"
Section 1.8.3, "ModBus Memory Formats"
Section 1.8.1

ModBus Function Codes

RUGGEDCOM devices support the following ModBus function codes for device management through ModBus:
NOTE
While RUGGEDCOM devices have a variable number of ports, not all registers and bits apply to all
products.
Registers that are not applicable to a particular device return a zero (0) value. For example, registers
referring to serial ports are not applicable to RUGGEDCOM switch devices.
Read Input Registers or Read Holding Registers — 0x04 or 0x03
Example PDU Request
Function Code
Starting Address
Number of Input Registers
Example PDU Response
Function Code
Byte Count
Number of Input Registers
a
The number of input registers
16
Data
1 Byte
2 Bytes
2 Bytes
1 Byte
1 Byte
a
N
x 2 Bytes
0x04(0x03)
0x0000 to 0xFFFF (Hexadecimal)
128 to 65535 (Decimal)
Bytes 0x0001 to 0x007D
0x04(0x03)
a
2 x N
ModBus Management Support
RUGGEDCOM ROS
User Guide