30 Fault Functions - ABB ACS150 series User Manual

0.37...4kw; 0.5...5 hp
Hide thumbs Also See for ACS150 series:
Table of Contents

Advertisement

Parameters in the Long parameter mode
Index Name/Selection

30 FAULT FUNCTIONS

3001
AI<MIN FUNCTION
0 = NOT SEL
1 = FAULT
2 = CONST SP 7
3 = LAST SPEED
3003
EXTERNAL FAULT 1
0 = NOT SEL
1 = DI1
2 = DI2
3 = DI3
4 = DI4
5 = DI5
-1 = DI1(INV)
-2 = DI2(INV)
-3 = DI3(INV)
-4 = DI4(INV)
-5 = DI5(INV)
3004
EXTERNAL FAULT 2
Description
Programmable protection functions
Defines the drive response if the analog input (AI) signal drops below the
fault limits and AI is used
• as the active reference source (group
• as the process or external PID controllers' feedback or setpoint source
(group
40 PROCESS PID SET
active.
3021
AI1 FAULT LIMIT sets the fault limits
Protection is inactive.
The drive trips on fault
AI1 LOSS
Fault limit is defined by parameter
The drive generates alarm
the value defined by parameter
defined by parameter
3021
WARNING! Make sure that it is safe to continue operation in case
the analog input signal is lost.
The drive generates alarm
the level the drive was operating at. The speed is determined by the average
speed over the previous 10 seconds. The alarm limit is defined by parameter
3021
AI1 FAULT LIMIT.
WARNING! Make sure that it is safe to continue operation in case
the analog input signal is lost.
Selects an interface for an external fault 1 signal.
Not selected
External fault indication through digital input DI1. 1: Fault trip on
1
(code: F0014). Motor coasts to stop. 0: No external fault.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
External fault indication through inverted digital input DI1. 0: Fault trip on
FAULT 1
(code: F0014). Motor coasts to stop. 1: No external fault.
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
Selects an interface for an external fault 2 signal.
See parameter
3003
EXTERNAL FAULT 1.
11 REFERENCE
1) and the corresponding PID controller is
(code: F0007) and the motor coasts to stop.
3021
AI1 FAULT LIMIT.
AI1 LOSS
(code: A2006) and sets the speed to
1208
CONST SPEED 7. The alarm limit is
AI1 FAULT LIMIT.
AI1 LOSS
(code: A2006) and freezes the speed to
Def
0 = NOT SEL
SELECT)
0 = NOT SEL
EXT FAULT
EXT
0 = NOT SEL
Actual signals and parameters
107